WD-TXT/24V

  •      

Product Description

Product parameter description of guide rail lightning arrester

Name

Type

Rated operating voltage(Un)

Maximum continuous operating voltage(Uc)

Rated load current(IL)

Nominal discharge current(ln)(8/20μs)

Maximum discharge current(nax)(8/20μs)

Voltage protection levelUp)

Transmission speed(Vs)

Insertion loss(Ae)

5V rail type signal lightning arrester

TL-TX/5

5V

8V

1A

5Ka

10Ka

≤13V

10M

≤0.3dB

12V rail type signal lightning arrester

TL-TX/12

12V

15V

1A

5Ka

10Ka

≤25V

10M

≤0.3dB

24V rail type signal lightning arrester

TL-TX/24

24V

30V

1A

5Ka

10Ka

≤60V

10M

≤0.3dB

4-20ma rail type signal lightning arrester

TL-TX/4-20

24V

30V

1A

5Ka

10Ka

≤60V

10M

≤0.3dB

36V rail type signal lightning arrester


TL-TX/36

36V

82V

1A

5Ka

10Ka

≤100V

10M

≤0.3dB

110V rail type signal lightning arrester

TL-TX/110

110V

180V

1A

5Ka

10Ka

≤230V

10M

≤0.3dB

12V rail type power lightning arrester

TL-DY/12

12V

18V

2A

5Ka

10Ka

≤60V

-

-

24V rail type power lightning arrester

TL-DY/24

24V

47V

2A

5Ka

10Ka

≤90V

-

-

48V rail type power lightning arrester

TL-DY/48

48V

82V

1A

5Ka

10Ka

≤130V

-

-

220V rail type power lightning arrester

TL-DY/220

220V

470V

1A

5Ka

10Ka

≤900V

-

-


Dimension specification of guide rail lightning arrester



Installation diagram of guide rail lightning arrester



Installation Instructions

This product is connected in series.
Please select a product with the same interface type as the protected device.
A-A/B-B of this product; (L/+) - (L/+)/(N/-) - (N/-) channels are one-to-one corresponding, and cross wiring is prohibited.
The "IN" of the lightning arrester is the input terminal connected to the "surge terminal" line, and the "OUT" is the output "equipment terminal" connected to the protected equipment.
The PE line of the lightning arrester must be reliably connected with the ground wire of the lightning protection system, and the connecting line is required to be short and thick.

The lightning arrester shall be tested regularly during its use. In case of failure, it shall be repaired or replaced in time to ensure the safety of the equipment